3 . I n s t r u c t i o n S e t

3 - 4 7 9

API Mnemonic

Operands

Function

271

D

BAND

Connect NO Contact in Series by
Specified Bit

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y

M S K H KnX KnY KnM KnS T C D E F

S

*

*

*

*

*

*

n

*

*

*

*

*

*

*

*

*

*

*

BAND: 5 steps

DBAND: 9 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S: Reference source device n: Reference bit

Explanations:

1.

For ES2/EX2 models, only V1.20 or above supports the function.

2.

Available range for the value in operand n: K0~K15 for 16-bit instruction; K0~K31 for 32-bit

instruction.

3.

BAND instruction is used to connect NO contact in series, whose state is defined by the

reference bit n in reference device D, i.e. if the bit specified by n is ON, the NO contact will be

ON, and vice versa.

Program Example:

X1

BAND

D0

K0

Y0

Instruction:

Operation:

LDI

X1

Load NC contact X1

BAND D0 K0 Connect NO contact in series

, whose state is defined by

bit0 of D0

OUT

Y0

Drive coil Y0