3 . I n s t r u c t i o n S e t

3 - 2 5 7

API Mnemonic Operands

Function

90

LDP

Rising–edge detection operation

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y

M S K H KnX KnY KnM KnS T C D E F

S *

*

*

*

*

*

LDP: 3 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S: device to be rising-edge triggered

Explanations:

LDP should be connected to the left side bus line. When the associated device S is driven from OFF

to ON, LDP will be ON for one scan cycle.

Program Example:

Ladder Diagram:

X0

X1

Y1

Instruction

Code: Operation:

LDP

X0

;

Load

rising-edge

contact

X0

AND

X1

; Connect NO contact X1 in series

OUT

Y1

; Drive Y1 coil

Points to Note:

1.

If the associated rising-edge contact is ON before PLC is power on, the contact will be

activated after PLC is power on.