3 . I n s t r u c t i o n S e t
3 - 2 5 7
API Mnemonic Operands
Function
90
LDP
Rising–edge detection operation
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices
Word devices
Program Steps
Type
OP
X Y
M S K H KnX KnY KnM KnS T C D E F
S *
*
*
*
*
*
LDP: 3 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: device to be rising-edge triggered
Explanations:
LDP should be connected to the left side bus line. When the associated device S is driven from OFF
to ON, LDP will be ON for one scan cycle.
Program Example:
Ladder Diagram:
X0
X1
Y1
Instruction
Code: Operation:
LDP
X0
;
Load
rising-edge
contact
X0
AND
X1
; Connect NO contact X1 in series
OUT
Y1
; Drive Y1 coil
Points to Note:
1.
If the associated rising-edge contact is ON before PLC is power on, the contact will be
activated after PLC is power on.