3 . I n s t r u c t i o n S e t

3 - 1 8 9

182. Please use transistor output for Y20 ~ Y23. Every pin 1, 2, 4, 8 shall be connected to a diode

(0.1A/50V) in series before connecting to the input terminals on PLC.

Wiring diagram of DIP switch:

S/S

X20

X21

X22

X23

X24

X25

X26

X27

Y23

Y22

Y21

Y20

C

1

2

4

8

1

2

4

8

PLC

10

10

10

10

0

1

2

3

10

0

10

1

10

2

10

3

0V

+24V

DIP switches for
BCD wiring

Must connect to a
diode (1N4148) in
series

The first group

The second group

Points to note:

When the terminals to be scanned are relay outputs, the following program methods can be applied:

183. When X30 = ON, DSW instruction will be executed. When X30 goes OFF, M10 remains ON

until the current scan cycle of output terminals is completed..

184. If the drive contact X30 uses button switch, M10 turns off only when the current scan cycle on

outputs is completed, so that a correct value from DIP switch can be read. In addition, the

continuous scan cycle on outputs will be performed only when the drive contact is pressed and

held. Applying this method can reduce the driving frequency of relay outputs so as to extend to

life-span of relays.

M10

DSW

X20

Y20

D20

K2

X30

SET

M10

M1029

RST

M10