beautypg.com

5 command code: 06, set content of single register – Delta DVP-ES2 User Manual

Page 619

background image

4 . C o m m u n i c a t i o n s

Field Name

ASCII

Force Data Lo

00

Error Check (LRC)

F6

END 1

0D (Hex)

END 0

0A (Hex)

4.5.5 Command Code: 06, Set content of single register

Example: Set content of register T0: 12 34 (Hex)

PC→PLC “: 01 06 06 00 12 34 AD CR LF”

Sent message:

Field Name

ASCII

STX :

Slave Address

01

Command code

06

Register Address Hi

06

Register Address Lo

00

Preset Data Hi

12

Preset Data Lo

34

Error Check (LRC)

AD

END 1

0D (Hex)

END 0

0A (Hex)

PLC→PC “: 01 06 06 00 12 34 AD CR LF”

Feedback message:

Field Name

ASCII

STX :

Slave Address

01

Command code

06

Register T0 Address Hi

06

Register T0 Address Lo

00

Preset Data Hi

12

Preset Data Lo

34

Error Check (LRC)

AD

END 1

0D (Hex)

END 0

0A (Hex)

4 - 1 7