D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
3-214
Flag
Function
Action
M1131
In ASCII mode, M1131 = ON only when MODRD/RDST/MODRW
data is being converted to HEX.
Supported communication instructions:
MODRD / RDST / MODRW
M1140
MODRD/MODWR/MODRW data receiving error
Supported communication instructions:
MODRD / MODWR / MODRW
M1141
MODRD/MODWR/MODRW parameter error
Supported communication instructions:
MODRD / MODWR/ MODRW
M1142
Data receiving error of VFD-A handy instructions.
Supported communication instructions:
FWD / REV / STOP / RDST / RSTEF
System
sets
M1143
ASCII / RTU mode selection. ON : RTU mode, OFF: ASCII mode.
Supported communication instructions:
RS / MODRD / MODWR / MODRW (When M1177 = ON, FWD /
REV / STOP / RDST / RSTEF can also be applied.
User sets
and resets
M1161
8/16-bit mode. ON: 8-bit mode. OFF: 16-bit mode
Supported communication instructions: RS
M1177
Enable the communication instruction for Delta VFD series inverter.
ON: VFD-A (Default), OFF: other models of VFD
Supported communication instructions:
FWD / REV / STOP / RDST / RSTEF
User sets
Special register
Function
D1038
Delay time of data response when PLC is SLAVE in COM2, COM3
RS-485 communication, Range: 0~10,000. (Unit: 0.1ms).
By using EASY PLC LINK in COM2, D1038 can be set to send next
communication data with delay. (unit: one scan cycle)
D1050~D1055
Converted data for Modbus communication data processing. PLC
automatically converts the ASCII data in D1070~D1085 into Hex data
and stores the 16-bit Hex data into D1050~D1055
Supported communication instructions: MODRD / RDST