D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3-214

Flag

Function

Action

M1131

In ASCII mode, M1131 = ON only when MODRD/RDST/MODRW

data is being converted to HEX.

Supported communication instructions:

MODRD / RDST / MODRW

M1140

MODRD/MODWR/MODRW data receiving error

Supported communication instructions:

MODRD / MODWR / MODRW

M1141

MODRD/MODWR/MODRW parameter error

Supported communication instructions:

MODRD / MODWR/ MODRW

M1142

Data receiving error of VFD-A handy instructions.

Supported communication instructions:

FWD / REV / STOP / RDST / RSTEF

System

sets

M1143

ASCII / RTU mode selection. ON : RTU mode, OFF: ASCII mode.

Supported communication instructions:

RS / MODRD / MODWR / MODRW (When M1177 = ON, FWD /

REV / STOP / RDST / RSTEF can also be applied.

User sets

and resets

M1161

8/16-bit mode. ON: 8-bit mode. OFF: 16-bit mode

Supported communication instructions: RS

M1177

Enable the communication instruction for Delta VFD series inverter.

ON: VFD-A (Default), OFF: other models of VFD

Supported communication instructions:

FWD / REV / STOP / RDST / RSTEF

User sets

Special register

Function

D1038

Delay time of data response when PLC is SLAVE in COM2, COM3

RS-485 communication, Range: 0~10,000. (Unit: 0.1ms).

By using EASY PLC LINK in COM2, D1038 can be set to send next

communication data with delay. (unit: one scan cycle)

D1050~D1055

Converted data for Modbus communication data processing. PLC

automatically converts the ASCII data in D1070~D1085 into Hex data

and stores the 16-bit Hex data into D1050~D1055

Supported communication instructions: MODRD / RDST