3 . I n s t r u c t i o n S e t

3 - 2 1 5

Special register

Function

D1070~D1085

Feedback data (ASCII) of Modbus communication. When PLC’s

RS-485 communication instruction receives feedback signals, the data

will be saved in the registers D1070~D1085 and then converted into

Hex in other registers.

RS instruction is not supported.

D1089~D1099

Sent data of Modbus communication. When PLC’s RS-485

communication instruction (MODRD) sends out data, the data will be

stored in D1089~D1099. Users can check the sent data in these

registers.

RS instruction is not supported

D1120

COM2 (RS-485) communication protocol. Refer to the following table in

point 4 for protocol setting.

D1121

COM1 (RS-232) and COM2 (RS-485) PLC communication address

when PLC is slave.

D1122

COM2 (RS-485) Residual number of words of transmitting data.

D1123

COM2 (RS-485) Residual number of words of the receiving data.

D1124

COM2 (RS-485) Definition of start character (STX) Refer to the

following table in point 3 for the setting.

Supported communication instruction: RS

D1125

COM2 (RS-485) Definition of first ending character (ETX1) Refer to the

following table in point 3 for the setting.

Supported communication instruction: RS

D1126

COM2 (RS-485) Definition of second ending character (ETX2) Refer to

the following table in point 3 for the setting.

Supported communication instruction: RS

D1129

COM2 (RS-485) Communication time-out setting (unit: ms). If users set

up time-out value in D1129 and the data receiving time exceeds the

time-out value, M1129 will be set ON and the error code K1 will be

stored in D1130. M1129 has to be reset manually when time-out status

is cleared.

D1130

COM2 (RS-485) Error code returning from Modbus. RS instruction is

not included.

Supported communication instructions: MODRD / MODWR / FWD /

REV / STOP / RDST / RSTEF / MODRW