3 . I n s t r u c t i o n S e t

3 - 2 9 1

Program Example:

Connect PLC to VFD series AC motor drive (ASCII mode, M1143 = OFF), (8-bit mode, M1161 = ON),

Write the data to be sent into registers starting from D100 in advance for reading 6 data from

address H0708 on VFD.

MOV

D1120

H86

M1002

SET

M1120

SET

M1122

MOV

D1129

K100

X10

M1123

RST

M1123

RS

D100

K17

D120

K35

pulse

Receiving completed

Processing received data

Set up communication protocol to 9600, 7, E, 1

Retain communication protocol

Set up communication time-out: 100ms

Sending request

Reset M1123

Write data to be sent in advance

Sending request pulse

PLC VFD, PLC sends: “: 01 03 07 08 0006 E7 CR LF ”

Registers for sent data (sending messages)

Register Data

Explanation

D100 low byte

‘: ’

3A H

STX

D101 low byte

‘0’

30 H

ADR 1

D102 low byte

‘1’

31 H

ADR 0

Address of AC motor
drive: ADR (1,0)

D103 low byte

‘0’

30 H

CMD 1

D104 low byte

‘3’

33 H

CMD 0

Command code:
CMD (1,0)

D105 low byte

‘0’

30 H

D106 low byte

‘7’

37 H

D107 low byte

‘0’

30 H

D108 low byte

‘8’

38 H

Starting data address

D109 low byte

‘0’

30 H

D110 low byte

‘0’

30 H

D111 low byte

‘0’

30 H

D112 low byte

‘6’

36 H

Number of data (words)

D113 low byte

‘E’

45 H

LRC CHK 0

D114 low byte

‘7’

37 H

LRC CHK 1

Error checksum: LRC
CHK (0,1)

D115 low byte

CR

D H

D116 low byte

LF

A H

END

The error checksum LRC CHK (0, 1) can be calculated by LRC instruction (8-bit mode, M1161 =

ON).

M1000

LRC

D101

K12

D113