beautypg.com

Delta DVP-ES2 User Manual

Page 248

background image

D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 1 3 2

¾

There are 6 software zone comparators available exclusively for zone compare operation,

hence the limit of 6 comparisons for zone compare does not include the comparisons of

DHSCS and DHSCR.

¾

SS2/SA2/SE does not support software counter C232.

5.

Explanations on hardware comparators for HSZ instruction:

¾

Corresponding table for hardware counters and comparators (It is not applicable to

VEP-SE):

A group

B group

Hardware counter

A1 A2 A3 A4 B1 B2 B3 B4

Counter No.

C243, C245~C248, C251,C252 C244, C249, C250, C253, C254

High-speed compare

Set/Reset

Shares 4 hardware

comparators for group A

Shares 4 hardware

comparators for group B

¾

Corresponding table for hardware counters and comparators (It is only applicable to

VEP-SE):

A group

B group

Hardware counter

A1 A2 B1 B2

Counter No.

C243, C245~C248, C251,C252

C244

High-speed

compare Set/Reset

Shares 2 hardware comparators

for group A

Shares 2 hardware

comparators for group B

¾

Block diagram of hardware counters and comparators:

Set /res et

Count
value

Count
value

Set /res et

Set /res et

Set /res et

Hardware
counter

Hardware
counter

Hardware
comparator

Hardware
comparator

A

A

B

B

A x 4

B x 4

B4

B1

A4

A1

A1

A4

B1

B4

I010

I040

I050

I080

¾

The two groups can only be used once for each group, occupying 2 comparators. For

example, when DHSZ instruction uses A3 and A4 of group A comparators, only the other

2 comparators (A1, A2) are available for DHSCS and DHSCR instructions.

¾

When DHSCS uses I030 or I040, comparators A3 and A4 are no longer available for

This manual is related to the following products: