Delta DVP-ES2 User Manual
Page 422
D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
3-306
API Mnemonic
Operands
Function
123
D EDIV P
Floating point division
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices
Word devices
Program Steps
Type
OP
X Y M S
K H
KnX
KnY KnM KnS T C D E F
S
1
*
*
*
S
2
*
*
*
D
*
DEADD, DEADDP: 13
steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S
1
: Dividend S
2
: Divisor D: Quotient and Remainder
Explanation:
1.
S
1
÷ S
2
= D. The floating point value in S
1
is divided by the floating point value in S
2
and the
result is stored in D. The division is conducted in binary floating point format.
2. If
S
1
or S
2
is designated as constant K or H, the instruction will convert the constant into a
binary floating point value before the operation.
3. If
S
2
= 0, operation error will occur, the instruction will not be executed
4.
Flags: M1020 (Zero flag), M1021 (Borrow flag) and M1022 (Carry flag)
If absolute value of the result exceeds max. floating point value, carry flag M1022 = ON.
If absolute value of the result is less than min. floating point value, borrow flag M1021 = ON.
If the conversion result is 0, zero flag M1020 = ON.
Program Example 1:
When X1 = ON, binary floating point value of (D1, D0) is divided by binary floating point (D11, D10)
and the quotient and remainder is stored in (D21, D20).
D0
DEDIV
X1
D10
D20
Program Example 2:
When X2 = ON, binary floating point value of (D1, D0) is divided by K1234 (automatically converted
to binary floating point value) and the result is stored in (D11, D10).
D0
DEDIV
X2
K1234
D10