Alarming

point>. This is also the location of the data point in the SmartServer tree.

Priority

Displays the alarm priority assigned to the data point in the Alarm Notifier:
Data Points
Web page.

Group

Displays the alarm group assigned to the data point in the Alarm Notifier:
Data Points
Web page.

Value

Displays the data point value that triggered the alarm.

If this alarm was triggered by a SNVT_alarm type data point, this will
be the value of the data point that caused the SNVT_alarm or update to
be sent.

If this alarm was triggered by a SNVT_alarm_2 data point, this value
will be the location of the alarm (for example, the location property for
an Alarm Generator).

If the data point is set to a preset value, the preset name will be
displayed instead of the actual value.

Unit

The unit string of the data point value that triggered the alarm condition. If
this alarm was triggered by a SNVT_alarm or SNVT_alarm_2 type data
point, this field will be blank.

Description

The alarm type or other description of the alarm entered in the Alarm
Notifier: Alarm Conditions
Web page.

5. Use the slide bar at the top to display the alarms reported during a specific time interval. You can

specify the length of the interval using the drop-down list directly below the slider. By default, the
Entire Range of when alarms were first and lastly reported is displayed.

6. Optionally, you can enter a comment, such as a description of how the alarm was resolved or

further maintenance work required, in the Comment box. The comment will be added to the
Alarm History log file. By default, the alarm description is displayed in this box.