beautypg.com

Creating modbus devices – Echelon SmartServer 2.2 User Manual

Page 273

background image

274

Using the SmartServer as Network Management Tool

Berndt Contec LAE Electronic LCD 15*

Cummins MOD-LON

Dixel XW570K

Honeywell 7800 series Burner controls with an S7810M Modbus Interface module

Leibert system 3 AHU with and OpenComms interface module

Schneider PM500*

Socomec A40*

Veris Industries H8035 Modbus Enercept kW/kWh meter

Wago System 750*

Yaskawa E7

* Device has a pre-defined template file loaded on the SmartServer which you can use to add it to the

SmartServer. See Using Device Templates in Chapter 4 for more information.

Each Modbus TCP/IP slave device must be added to a separate channel. Adding more than one
Modbus TCP device to a Modbus TCP/IP channel generates unexpected results such as all points
being mapped to the first device defined on the channel. These errors occur even if the Modbus
TCP/IP addresses are unique.

Creating Modbus Devices

To create a Modbus device, follow these steps:

1. Right-click a Modbus channel, and then select Add Device on the shortcut menu.

2. The Add Device dialog opens.