Viewing m-bus devices – Echelon SmartServer 2.2 User Manual
Page 291
292
Using the SmartServer as Network Management Tool
Medium
Displays the device’s medium ID as a 1-byte enumeration that identifies
the device functionality. The following is a list of possible medium IDs:
Value Identifier
Notes
-1
MED_NUL
Invalid
0
MED_OTHER
Others
1
MED_OIL
Oil
2
MED_ELECTRICITY
Electricity
3
MED_GAS
Gas
4
MED_RETURN_TEMP
5
MED_STEAM
Steam
6
MED_HOT_WATER
Hot water
7
MED_WATER
Water
8
MED_HEAT_METER
Heat meter
9
MED_COMPRESSED_AIR
Compressed-air
10
MED_RES1
Reserved
11
MED_RES2
Reserved
12
MED_FLOW_TEMP
Flow temperature,
outgoing/supply temperature
13
MED_RES3
Reserved
14
MED_SYS_BUS
System / Bus
15
MED_UNKNOWN
Unknown
Version
Specifies the generation or version of the device as 1-byte char. This
value depends on the manufacturer.
5. Click Submit.
6. Create and configure a type translator to integrate the data generated by an M-Bus device into a
L
ON
W
ORKS
network. See Integrating M-Bus Devices With a Type Translator in Chapter 11 for
more information on how to do this.
Viewing M-Bus Devices
You can view and configure the all the M-Bus devices in your network or on a specific channel using
the Overview – Devices Web page. This Web page displays the primary or secondary address, parent
channel, and name of each M-Bus device. To view M-Bus devices with the Overview – Devices Web
page, follow these steps:
1. To configure the primary or secondary addresses, or names of the M-Bus devices, click the Driver
option at the top of the navigation pane on the left side of the SmartServer Web interface.
2. Right-click the network or a M-Bus channel in the SmartServer tree, point to Overview, and then
select Devices.