Alarming

3. Configure the following properties of the selected input points:

Data Point

Displays the name of the data point being monitored using the following
format: <network>/<channel>/<device>/<functional block>/<data point>.
This is also the location of the data point in the SmartServer tree.

Priority

Enter the priority of the alarm associated with this input point. This value
may range from 0 to 255 (highest to lowest priority).

This property has no effect on the alarm function, but it can be included in
e-mails to provide the recipient with more information, and it can be used as
a sort field when viewing alarm logs in Excel.

Alarm Group

Enter an alarm group number to be assigned to the input point. This value
can be from 1 to 127. A value of 0 indicates the alarm has not been assigned
to a group.

This property has no effect on the alarm function, but it can be included in
e-mails to provide the recipient with more information, and it can be used as
a sort field when viewing alarm logs in Excel.

4. Select the Show Advanced check box to configure the following advanced properties:

Disabled

Disables alarm notifications for the input point. No alarm notifications will
be sent for the input point. This check box is cleared by default.

Clear Required

Requires the input point to be manually cleared to end the alarm condition.
You can clear alarms in the Alarm Notifier: Summary Web page, as
described later in this chapter. This may be useful for keeping an alarm
active, even when the alarm condition has returned to normal. This option is
cleared by default.

Acknowledgement
Required

Requires the input point to be manually acknowledged to end the alarm
condition. You can acknowledge alarms in the Alarm Notifier: Summary
Web page, as described later in this chapter. This may be useful for keeping
an alarm active, even when the alarm condition has returned to normal. This
option is selected by default.

Store Only Most
Recent

Stores in the Alarm Summary log only the most recent alarm received on the
input point. All alarms are stored in the Alarm History log, regardless of
whether this check box is selected. This option is selected by default.