Checking device status – Echelon SmartServer 2.2 User Manual
Page 308
![background image](/manuals/735727/308/background.png)
SmartServer
2.2 User’s Guide
309
3. Loads and instantiates the device interface (if the Smart Network Management check box is
selected for the Template property).
a. The SmartServer first attempts to load the device template (.XML file) in the
/config/template/lonworks
folder on the flash disk that has a matching program ID.
b. If the SmartServer cannot find a matching device template, the SmartServer loads the device
interface (XIF) file in the /LonWorks/import directory that has a matching program ID.
c. The SmartServer creates all the functional blocks and data points defined by the device
interface.
4. Re-commissions the device. Commissioning downloads network configuration data and
application configuration data to the device.
5. Writes default configuration property values to the device.
6. Resets the device, which starts the device application.
7. Sets the device application online.
Checking Device Status
You can use the LON Command Queue Web page to check the status of the management commands
you have submitted for one or more devices. To use this Web page, follow these steps:
1. Right-click the SmartServer icon, point to Setup, and then click LON Command Queue on the
shortcut menu. Alternatively, you can open the Setup menu and then click LON Command
Queue.
2. The LON Command Queue Web page opens.