Connect to the kinetix 300 drive – Rockwell Automation 193 Drives and Motion Accelerator Toolkit Quick Start User Manual

Page 313

background image

Rockwell Automation Publication IASIMP-QS019E-EN-P - August 2013

313

Controller, Network, and Device Configuration Without the DMAT Wizard

Appendix G

Connect to the Kinetix 300 Drive

Configuration of the Kinetix 300 drive is performed over the standard 10/100 Mbps Ethernet communication
port using MotionView OnBoard software contained within the drive itself. To access the MotionView software,
the drive and your personal computer must be configured to operate on the same network.

1.

Run a Java enabled web browser such as Internet Explorer.

2.

Enter the drive’s IP address into the browser.

The File Download dialog box opens.

3.

Click Open.

The Security Warning dialog box may open.

4.

If the Security Warning dialog box opens, click
Run.

The Hazard of unexpected motor starting dialog box opens.

5.

Read the cautionary text and Click Yes, I have.

The MotionView software opens.

6.

Click Connect

.

The Connection dialog box opens.

TIP

The Kinetix 300 drive’s IP address is scrolling across the keypad display. The default IP address for each Kinetix 300 drive
(192.168.124.200) is used in this connection example.