Commissioning smc-50 soft starter modules, Apply power to the relay, Status indicators – Rockwell Automation 193 Drives and Motion Accelerator Toolkit Quick Start User Manual
Page 166: Startup routines

166
Rockwell Automation Publication IASIMP-QS019E-EN-P - August 2013
Chapter 6
System Commissioning
Commissioning SMC-50 Soft Starter Modules
These commissioning procedures apply specifically to the SMC-50 soft starter modules.
For more information on drive commissioning for SMC-50 soft starters, refer to the appropriate user manual
listed in
Apply Power to the Relay
Apply power to the SMC-50 soft starter module.
Status Indicators
The SMC-50 soft starter has one status indicator on the front of the module that displays fault and alarm codes
as described in the following table.
SMC-50 Module Status Indicator
Startup Routines
Start-up routines are available for the SMC 50 soft starter through the Start-Up Configuration Tool on the
20-HIM-A6, 20-HIM-C6S module, or the Start-Up Wizard available in DriveExplorer software. The start-up
wizard steps through general configuration.
For more information on the SMC-50 soft-starter startup routine, refer to the SMC-50 Solid-state Smart Motor
Controller User Manual, publication
Color
Device Mode
SMC-50 Module Status
Green
Running
Running without an alarm
Green/amber
Running
Running with an alarm
Green/flashing
Ready
Ready (no inhibit and no fault) without an alarm
Amber/flashing
Ready
Ready (no inhibit and no fault) with tuning enabled on the next start
Amber
Ready
Ready with alarm (no tuning enabled)
Red/amber
Inhibit
Inhibited, cannot start due to a Stop command
Red
Faulted
A non-resettable fault has occurred
Red/flashing
Faulted
A resettable fault has occurred
Red/green
Download
Firmware is being downloaded
Status Indicator
SMC-50 Soft
Starter Module
- 150 Drives and Motion Accelerator Toolkit Quick Start 21G Drives and Motion Accelerator Toolkit Quick Start 20G Drives and Motion Accelerator Toolkit Quick Start 20F Drives and Motion Accelerator Toolkit Quick Start 2097 Drives and Motion Accelerator Toolkit Quick Start 2094 Drives and Motion Accelerator Toolkit Quick Start