Delete unused alarm triggers – Rockwell Automation 193 Drives and Motion Accelerator Toolkit Quick Start User Manual
Page 128

128
Rockwell Automation Publication IASIMP-QS019E-EN-P - August 2013
Chapter 5
FactoryTalk View ME Configuration
Delete Unused Alarm Triggers
Follow these steps to delete any alarm triggers for hardware devices not used in your application. This could
improve performance of your PanelView Plus terminal communication.
1.
Expand the Alarms folder.
2.
Double-click Alarm Setup.
The Alarm Setup dialog box opens.
3.
Click the Triggers tab.
4.
Select any unused alarm trigger tags from the Select trigger organizer.
Unused trigger tags are any associated devices not configured in your Logix Designer project.
For the Widg-O-matic application example, these alarm triggers are used, so all other trigger tags can be
removed.
5.
Click Remove.
6.
and
for all unused trigger tags.
7.
Click OK in the Alarm Setup dialog box to save edits.
IMPORTANT
Deleting Unused Alarm Triggers is optional and applies only if you have imported the Alarm Setup file in the last section.
Alarm Triggers Used
PowerFlexAlarmTrigger
ModuleAlarmTrigger
CIPMotionTrigger
K300AlarmTrigger
- 150 Drives and Motion Accelerator Toolkit Quick Start 21G Drives and Motion Accelerator Toolkit Quick Start 20G Drives and Motion Accelerator Toolkit Quick Start 20F Drives and Motion Accelerator Toolkit Quick Start 2097 Drives and Motion Accelerator Toolkit Quick Start 2094 Drives and Motion Accelerator Toolkit Quick Start