beautypg.com

Crimping, D.3 ul and csa standards – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 535

background image

Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

5A0077

R/L1, S/L2, T/L3

3

10 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

3

10 to 4/0

⊖, ⊕1

3 to 4/0

⊕3

6 to 4/0

4

4

5A0099

R/L1, S/L2, T/L3

1/0

10 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

1

10 to 4/0

⊖, ⊕1

2 to 4/0

⊕3

4 to 4/0

4

4

5A0125

R/L1, S/L2, T/L3

2/0

1 to 300

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

2/0

1 to 300

⊖, ⊕1

2/0 to 3/0

⊕3

1 to 1/0

3

4 to 300

5A0145

R/L1, S/L2, T/L3

3/0

2/0 to 300

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

3/0

2/0 to 300

⊖, ⊕1

3/0 to 4/0

⊕3

1/0 to 2/0

3

4 to 300

5A0192

R/L1, S/L2, T/L3

300

2/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

250

2/0 to 600

⊖, ⊕1

2/0 to 400

⊕3

2/0 to 250

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

5A0242

R/L1, S/L2, T/L3

400

2/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

350

2/0 to 600

⊖, ⊕1

2/0 to 500

⊕3

250 to 300

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

Closed-Loop Crimp Terminal Recommendations

To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main

circuit terminals on models 2A0110 to 2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242. Use only the tools recommended

by the terminal manufacturer for crimping. Yaskawa recommends crimp terminals made by JST and Tokyo DIP (or equivalent)

for the insulation cap.

Table D.7

matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp

terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge

and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
Wire gauge values shown in bold italic are the recommended values. Refer to local codes for proper selections.

Table D.7 Closed-Loop Crimp Terminal Size

Drive Model

Wire Gauge (AWG, kcmil)

Screw

Size

Crimp

Terminal

Model Number

Tool

Insulation Cap

Model No.

Code

<1>

R/L1, S/L2, T/L3 U/T1, V/T2, W/T3

Machine No.

Die Jaw

200 V Class

2A0004

2A0006

2A0008

2A0010

14

M4

R2-4

YA-4

AD-900

TP-003

100-054-028

12

R5.5-4

TP-005

100-054-029

10

D.3 UL and CSA Standards

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

535

D

Standards Compliance

This manual is related to the following products: