No.

Name

Setting Range

Default

L3-11

Overvoltage Suppression Function Selection

0, 1

0

Setting 0: Disabled

The regenerative torque limit and the output frequency are not adjusted. A regenerative load may trip the drive with an

overvoltage fault. Use this setting if dynamic braking options are installed.

Setting 1: Enabled

When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by decreasing the regenerative

torque limit and increasing the output frequency.

n

L3-17: Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention

Sets the target DC bus voltage level used by the overvoltage suppression function (L3-11 = 1), Intelligent Stall Prevention

during deceleration (L3-04 = 2).

No.

Name

Setting Range

Default

L3-17

Target DC Bus Voltage for Overvoltage Suppression

and Stall Prevention

150 to 400 Vdc

<1>

375 Vdc

<1> <2>

<1> Values are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but set the

value below 1040 Vdc (overvoltage protection level).

<2> This value is initialized when E1-01 is changed.

n

L3-20: DC Bus Voltage Adjustment Gain

Determines the proportional gain used by overvoltage suppression (L3-11 = 1), Single Drive KEB 2 (L2-29 = 1), KEB Ride-

Thru 2 (H1-oo = 7A or 7B) ,and Intelligent Stall Prevention during deceleration (L3-04 = 2) to control the DC bus voltage.

No.

Name

Setting Range

Default

L3-20

DC Bus Voltage Adjustment Gain

0.00 to 5.00

1.00

Adjustment for Single Drive KEB 2 (L2-29 = 1) and Intelligent Stall Prevention During Deceleration

• Increase this setting slowly in steps of 0.1 if overvoltage or undervoltage occurs at the beginning of deceleration.
• Decrease this setting if there is a fair amount of speed or torque ripple.

Adjustment for Overvoltage Suppression

• Increase this setting slowly in steps of 0.1 if overvoltage suppression is enabled (L3-11 = 1) and a sudden increase in a

regenerative load causes an overvoltage fault.

• Decrease this setting if there is a fair amount of speed or torque ripple.

n

L3-21: Accel/Decel Rate Calculation Gain

Determines the proportional gain used by overvoltage suppression (L3-11 = 1), Single Drive KEB 2 (L2-29 = 1), and Intelligent

Stall Prevention during deceleration (L3-04 = 2) to calculate acceleration and deceleration rates.

No.

Name

Setting Range

Default

L3-21

Accel/Decel Rate Calculation Gain

0.10 to 10.00

1.00

Adjustment for Single Drive KEB 2 (L2-29 = 1) and Intelligent Stall Prevention During Deceleration

• Reduce L3-21 in steps of 0.05 if there is a fairly large speed or current ripple.
• Small reductions of L3-21 can help solve problems with overvoltage and overcurrent.
• Decreasing this setting too much can cause slow DC bus voltage control response and may also lengthen deceleration times

beyond optimal levels.

Adjustment for Overvoltage Suppression

• Increase this setting in steps of 0.1 if overvoltage occurs as a result of a regenerative load when overvoltage suppression is

enabled (L3-11 = 1).

• Decrease L3-21 in steps of 0.05 if there is a fairly large speed ripple when overvoltage suppression is enabled.

n

L3-23: Automatic Reduction Selection for Stall Prevention during Run

Reduces the Stall Prevention during run level in the constant power range.

5.8 L: Protection Functions

250

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual