Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 402

u
Three-Phase 600 V Class Drive Models 5A0003 to 5A0032
Table A.7 Power Ratings (Three-Phase 600 V Class)
Item
Specification
Drive Models
5A0003 5A0004 5A0006 5A0009 5A0011 5A0017 5A0022 5A0027 5A0032
Maximum Applicable
Motor Capacity (HP)
<1>
ND Rating
2
3
5
7.5
10
15
20
25
30
Input
Input Current (A)
<2>
ND Rating
3.6
5.1
8.3
12
16
23
31
38
45
Rated Voltage
Rated Frequency
Three-phase 500 to 600 Vac 50/60 Hz
Allowable Voltage Fluctuation
-10 (-15) to +10%
Allowable Frequency
Fluctuation
±5%
Input Power
(kVA)
ND Rating
4.1
5.8
9.5
14
18
26
35
43
51
Output
Rated Output
Capacity (kVA)
<3>
ND Rating
<4>
2.7
3.9
6.1
9
11
17
22
27
32
Rated Output
Current (A)
ND Rating
<4>
2.7
3.9
6.1
9
11
17
22
27
32
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable between 1 and 15 kHz
<4>
User-adjustable between 1 and 10 kHz
<4>
Maximum Output Voltage (V)
Three-phase 500 to 600 V (proportional to input voltage)
Maximum Output
Frequency (Hz)
400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings
raise the carrier frequency and require current derating.
A.1 Power Ratings
402
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual