Stall Prevention Level
During Acceleration

L3-02

L3-02

-15%

Output current

Output frequency

Time

Time

Controls the output frequency
to prevent the motor from stalling

Figure 5.77 Stall Prevention During Acceleration for Induction Motors

Setting 2: Intelligent Stall Prevention

The drive disregards the selected acceleration time and attempts to accelerate in the minimum time. The acceleration rate is

adjusted so the current does not exceed the value set to parameter L3-02.

n

L3-02: Stall Prevention Level during Acceleration

Sets the output current level at which the Stall Prevention during acceleration is activated.

No.

Name

Setting Range

Default

L3-02

Stall Prevention Level during Acceleration

0 to 150%

<1>

<1>

<1> The upper limit and default value is determined by parameter L8-38, Carrier Frequency Reduction.

• Lower L3-02 if stalling occurs when using a motor that is relatively small compared to the drive.
• Also set parameter L3-03 when operating the motor in the constant power range.

n

L3-03: Stall Prevention Limit during Acceleration

The Stall Prevention level is automatically reduced when the motor is operated in the constant power range. L3-03 sets the

lower limit for this reduction as a percentage of the drive rated current.

No.

Name

Setting Range

Default

L3-03

Stall Prevention Limit during Acceleration

0 to 100%

50%

Stall Prevention level during Acceleration

Output frequency

L3-03

E1-06

Base frequency

L3-02

Figure 5.78 Stall Prevention Level and Limit During Acceleration

5.8 L: Protection Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

247

5

Parameter Details