Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPM (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)
Setting 15: Hg (Inches of Mercury)
Setting 25: None

n

b5-42: PI Output Monitor Calculation Method

No.

Name

Setting Range

Default

b5-42

PI Output Monitor Calculation Method

0 to 3

0

Setting 0: Linear

The monitor displays PID output.

Setting 1: Square Root

The monitor displays square root PID output.

Setting 2: Quadratic

The monitor displays 1/(PID output)

2

Setting 3: Cubic

The monitor displays 1/(PID output)

3

Note:

Used for U5-14 and U5-15 only.

n

b5-43/b5-44: Custom PI Output Monitor Setting 1/2

Set the maximum monitor value at maximum frequency. U5-14 and U5-15 show Custom PI output. U5-14 shows the upper

4 digits and U5-15 shows the lower 4 digits. It shows 999999.99 maximum.

No.

Name

Setting Range

Default

b5-43

PI Output 2 Monitor Max Upper 4 Digits

0 to 9999

0

b5-44

PI Output 2 Monitor Max Lower 4 Digits

0 to 99.99

0

Note:

Used for U5-14 and U5-15 only.

n

b5-45: PI Output 2 Monitor Minimum

b5-14 shows Custom PI Output. b5-45 sets the minimum display value at zero speed. This function is effective when b5-42

is set to 0 (Linear).

No.

Name

Setting Range

Default

b5-45

PI Output 2 Monitor Minimum

0 to 999.9

0

Note:

Used for U5-14 and U5-15 only.

n

b5-47: PID Output Reverse Selection 2

Determines whether a negative PID output reverses the direction of drive operation. When the PID function is used to trim

the frequency reference (b5-01 = 3 or 4), this parameter has no effect and the PID output will not be limited

(same as b5-11 = 1).

5.2 b: Application

172

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual