beautypg.com

Broadcast messages – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 510

background image

Register No.

Contents

00E5H

oFC3x Contents (CN5-C)
bit 0

Comm. ID Error (oFC30)

bit 1

Model Code Error (oFC31)

bit 2

Sumcheck Error (oFC32)

bit 3

Comm. option timeout waiting for response (oFC33)

bit 4

MEMOBUS Timeout (oFC34)

bit 5

Drive timeout waiting for response (oFC35)

bit 6

CI Check Error (oFC36)

bit 7

Drive timeout waiting for response (oFC37)

bit 8

Control Command Selection Error (oFC38)

bit 9

Drive timeout waiting for response (oFC39)

bit A

Control Response Selection 1 Error (oFC40)

bit B

Drive timeout waiting for response (oFC41)

bit C

Control Response Selection 2 Error (oFC42)

bit D

Control Response Selection Error (oFC43)

bit E, F

Reserved

00E6H to 00FFH

Reserved

<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive is set for

a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motor capacity is
higher than 11 kW.

Refer to Power Ratings on page 396

.

<3> Communication error contents are saved until the fault is reset.
<4> Set the number of motor poles to parameter E2-04.

u

Broadcast Messages

Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not

respond.

Register No.

Contents

0001H

Digital Input Command
bit 0

Forward Run (0: Stop 1: Run)

bit 1

Direction Command (0: Forward, 1: Reverse)

bit 2, 3

Reserved

bit 4

External Fault

bit 5

Fault Reset

bit 6 to B

Reserved

bit C

Multi-Function Digital Input S5

bit D

Multi-Function Digital Input S6

bit E

Multi-Function Digital Input S7

bit F

Multi-Function Digital Input S8

0002H

Frequency Reference

30000/100%

C.9 MEMOBUS/Modbus Data Table

510

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

This manual is related to the following products: