5.6 F: Option Settings

u

F4: Analog Monitor Card Settings

These parameters set the drive for operation with the analog output option card AO-A3. Refer to the instruction manual

packaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.

n

F4-01, F4-03: Terminal V1, V2 Monitor Selection

Selects the data to output from analog terminal V1. Enter the final three digits of Uo-ooto determine which monitor data

is output from the option card. Some monitors are only available in certain control modes.

No.

Parameter Name

Setting Range

Default

F4-01

Terminal V1 Monitor Selection

000 to 999

102

F4-03

Terminal V2 Monitor Selection

000 to 999

103

n

F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Monitor Gain and Bias

Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set as

a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is limited to

10 V.

No.

Parameter Name

Setting Range

Default

F4-02

Terminal V1 Monitor Gain

-999.9 to 999.9%

100.0%

F4-04

Terminal V2 Monitor Gain

-999.9 to 999.9%

50.0%

F4-05

Terminal V1 Monitor Bias

-999.9 to 999.9%

0.0%

F4-06

Terminal V2 Monitor Bias

-999.9 to 999.9%

0.0%

Using Gain and Bias to Adjust Output Signal Level

The output signal is adjustable while the drive is stopped.

Terminal V1

1.

View the value set to F4-02 (Terminal V1 Monitor Gain) on the digital operator. A voltage equal to 100% of the

parameter being set in F4-01 will be output from terminal V1.

2.

Adjust F4-02 viewing the monitor connected to the terminal V1.

3.

View the value set to F4-05 on the digital operator, terminal V1 will output a voltage equal to 0% of the parameter

being set in F4-01.

4.

Adjust F4-05 viewing the output signal on the terminal V1.

Terminal V2

1.

View the value set to F4-02 (Terminal V2 Monitor Gain) on the digital operator. A voltage equal to 100% of the

parameter being viewed in F4-03 will be output from terminal V2.

2.

Adjust F4-04 viewing the monitor connected to the terminal V2.

3.

View the value set to F4-06 on the digital operator, terminal V2 will output a voltage equal to 0% of the parameter

being set in F4-03.

4.

Adjust F4-06 viewing the output signal on the terminal V2.

n

F4-07, F4-08: Terminal V1, V2 Signal Level

Sets the output signal level for terminals V1 and V2.

No.

Parameter Name

Setting Range

Default

F4-07

Terminal V1 Signal Level

0, 1

0

F4-08

Terminal V2 Signal Level

0, 1

0

Setting 0: 0 to 10 V

Setting 1: -10 to 10 V

5.6 F: Option Settings

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

197

5

Parameter Details