11 s: special application, Timing charts – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 277

background image

Mon

0:00

Sequence Timer 2

1:00

(cont.)

2:00
3:00
4:00
5:00
6:00

Sequence Timer 2

Run at d1-03

7:00
8:00
9:00

10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00

Sequence Timer 1

Run at d1-01

Sun

Sat

Fri

Thur

Wed

Tue

Figure 5.88 Sequence Timer Example 2

0:00
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00

Sequence Timer 3

Run at d1-03

10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00

Mon

Sun

Sat

Fri

Thur

Wed

Tue

Sequence Timer 1

Run at d1-01

Sequence Timer 2

Run at d1-02 with PI control disabled

Figure 5.89 Sequence Timer Example 3

Timing Charts

In

Figure 5.90

S2-04 = 1, S2-05 = 0, S2-09 = 2, S2-10 = 1. It shows the effect of Run command and sequence timer disable

input.

Run

command

Output

frequency

Seq Timer Disable

multi-function input

d1-01

d1-02

Sequence Timer 1

multi-function output

Sequence Timer 2

multi-function output

Figure 5.90 Timing Chart 1

5.11 S: Special Application

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

277

5

Parameter Details