5.5 E: Motor Parameters

E parameters cover V/f pattern and motor data settings.

u

E1: V/f Pattern for Motor 1

n

E1-01: Input Voltage Setting

Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the nominal

voltage of the AC power supply.

NOTICE:

Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the

protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.

No.

Parameter Name

Setting Range

Default

E1-01

Input Voltage Setting

155 to 255 V

<1>

230 V

<1>

<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.

E1-01 Related Values

The input voltage setting determines the overvoltage and undervoltage detection levels, the operation levels of the braking

transistor, the KEB function, and the overvoltage suppression function.

Voltage Setting Value of

E1-01

ov Detection Level/Dynamic

Braking Transistor Detection

Level

<1>

(rr Detection Level)

(Approximate Values)

Uv Detection Level

(L2-05)

Desired DC Bus Voltage

during KEB (L2-11)

ov Suppression /

Stall Prevention Level

(L3-17)

200 V

Class

All settings

410 V / 394 V

190 V

260 V

375 V

400 V

Class

setting ≥ 400 V

820 V / 788 V

380 V

500 V

750 V

setting < 400 V

820 V / 788 V

350 V

460 V

750 V

600 V

Class

All settings

1178 V / 1132 V

475 V

635 V

930 V

<1> The braking transistor operation levels are valid for the drive internal braking transistor. When using a CDBR braking unit, refer to instruction

manual TOBPC72060000 or TOBPC72060001.

n

V/f Pattern Settings (E1-03)

The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference. There are 15 different predefined

V/f patterns (setting 0 to E) from which to select, each with varying voltage profiles, saturation levels (frequency at which

maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern is available (setting F) that

requires the user to create the pattern using parameters E1-04 through E1-10.

n

E1-03: V/f Pattern Selection

Selects the V/f pattern for the drive and motor from 15 predefined patterns or creates a custom V/f pattern.

No.

Parameter Name

Setting Range

Default

E1-03

V/f Pattern Selection

0 to F

F

<1>

<1> Parameter is not reset to the default value when the drive is initialized using A1-03.

Setting a Predefined V/f Pattern (Setting 0 to E)

Choose the V/f pattern that best meets the application demands from

Table 5.16

. These settings are available only in

V/f Control modes. Set the correct value to E1-03. Parameters E1-04 to E1-13 can only be monitored, not changed.

Note:

1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Drive initialization does not reset parameter E1-03.

5.5 E: Motor Parameters

190

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual