Min output

frequency

100%

(Max output

frequency)

Output frequency

when Stop command

was entered

Run wait time t

Active deceleration time

Min Baseblock Time (L2-03)

Figure 5.7 Run Wait Time Depending on Output Frequency

n

b1-04: Reverse Operation Selection

Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause

problems (e.g., air handling units, pumps, etc.).

No.

Parameter Name

Setting Range

Default

b1-04

Reverse Operation Selection

0, 1

0

Setting 0: Reverse operation enabled

Possible to operate the motor in both forward and reverse directions.

Setting 1: Reverse operation disabled

Drive disregards a Reverse run command or a negative frequency reference.

n

b1-07: LOCAL/REMOTE Run Selection

The drive has three separate control sources that can be switched using digital inputs (H1-oo = 1 (LOCAL/REMOTE

Selection) or 2 (External reference 1/2)) or the LO/RE key on the digital operator.

Refer to Setting 1: LOCAL/REMOTE

Selection on page 205

,

Refer to Setting 2: External Reference 1/2 Selection on page 206

and

Refer to o2-01: LO/RE

(LOCAL/REMOTE) Key Function Selection on page 268

for details.

• LOCAL: Digital operator. The digital operator sets the frequency reference and Run command.
• REMOTE: External reference 1. The frequency reference and Run command source are set by b1-01 and b1-02.
• REMOTE: External reference 2. The frequency reference and Run command source are set by b1-15 and b1-16.
When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run command

may already be present at the location at which the source is being switched. In this case, use parameter b1-07 to determine

how the Run command is treated.

No.

Parameter Name

Setting Range

Default

b1-07

LOCAL/REMOTE Run Selection

0, 1

0

Setting 0: Run command must be cycled

When the Run command source differs between the old source and the new source (e.g., the old source was the terminals and

the new source is serial communication), and the Run command is active at the new source as the switchover occurs, the drive

will not start or the drive will stop operation if it was previously running. The Run command must be cycled at the new source

to restart the drive.

Setting 1: Accept Run command at the new source

When the Run command is active at the new source, the drive starts or continues operation if it was previously running.

WARNING!

Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel

from rotating machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.

n

b1-08: Run Command Selection while in Programming Mode

As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being used

to adjust parameters in Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning Mode).

If required by the application, set b1-08 to allow the drive to run while in Programming Mode.

No.

Parameter Name

Setting Range

Default

b1-08

Run Command Selection while in Programming Mode

0 to 2

0

5.2 b: Application

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

151

5

Parameter Details