beautypg.com

Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 435

background image

H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

Description

Page

41

Reverse run command

(2-Wire sequence)

Open: Stop

Closed: Reverse run

Note:

Cannot be set together with settings 42 or 43.

211

42

Run command

(2-Wire sequence 2)

Open: Stop

Closed: Run

Note:

Cannot be set together with settings 40 or 41.

211

43

FWD/REV command

(2-Wire sequence 2)

Open: Forward

Closed: Reverse

Note:

Determines motor direction, but does not issue a Run command. Cannot be set

together with settings 40 or 41.

211

47

Node setup

Closed: Node setup for SI-S3 enabled.

211

51

Sequence Timer Disable

Closed: Drive ignores sequence timers and runs normally (based on b1-02/b1-16 source).

211

52

Sequence Timer Cancel

Closed: When the input changes from open to closed, the currently active sequence timer is

disabled. Operation will resume with the next scheduled sequence timer. Cycling the Run

command after the current sequence timer has been canceled will re-enable the sequence

timer.

211

60

DC Injection Braking command

Closed: Triggers DC Injection Braking.

211

61

External Speed Search

command 1

Closed: Activates Current Detection Speed Search from the maximum output frequency

(E1-04).

211

62

External Speed Search

command 2

Closed: Activates Current Detection Speed Search from the frequency reference.

211

63

Field weakening

Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.

212

65

KEB Ride-Thru 1 (N.C.)

Open: KEB Ride-Thru 1 enabled.

212

66

KEB Ride-Thru 1 (N.O.)

Closed: KEB Ride-Thru 1 enabled.

212

67

Communications test mode

Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the test

completes successfully.

212

68

High Slip Braking (HSB)

Closed: Activates High Slip Braking to stop the drive during a Run command.

212

6A

Drive enable

Open: Drive disabled. If this input is opened during run, the drive will stop as specified by

b1-03.

Closed: Ready for operation.

212

75

Up 2 command

Used to control the bias added to the frequency reference by the Up/Down 2 function. The

Up 2 and Down 2 commands must always be used in conjunction with one another.

212

76

Down 2 command

Used to control the bias added to the frequency reference by the Up/Down 2 function. The

Up 2 and Down 2 commands must always be used in conjunction with one another.

212

7A

KEB Ride-Thru 2 (N.C.)

Open: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB

Ride-Thru 2.

213

7B

KEB Ride-Thru 2 (N.O.)

Closed: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB

Ride-Thru 2.

213

A8

Secondary PI Disable (N.O.)

Closed: Disables the secondary PI controller. Output behavior depends on the setting of

S3-12.

213

A9

Secondary PI Disable (N.C.)

Closed: Enables the secondary PI controller. Output behavior depends on the setting of S3-12

when open.

213

AA

Secondary PI Inverse Operation

Closed: Changes the sign of the secondary PI controller input (reverse acting PI control).

213

AB

Secondary PI Integral Reset

Closed: Resets the secondary PI controller integral value.

213

AC

Secondary PI Integral Hold

Closed: Locks the value of the secondary PI controller integral value.

213

AD

Select Secondary PI Parameters

Closed: Uses the secondary PI controller Proportional and Integral adjustments (S3-06 and

S3-07) instead of the primary PI controller Proportional and Integral adjustments (b5-02 and

b5-03). Only valid when S3-01 = 0 (secondary PI controller disabled).

Note:

This multi-function input has no effect on the secondary PI controller. It is only

used for the primary PI controller (b5-oo).

214

AF

Emergency Override Forward Run Closed: Run the drive forward using the speed set in S6-02.

214

B0

Emergency Override Reverse Run Closed: Run the drive in reverse using the speed set in S6-02.

214

B.7 H Parameters: Multi-Function Terminals

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

435

B

Parameter List

This manual is related to the following products: