beautypg.com

B.15 defaults by drive model – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 473

background image

No.

Name

Unit

Default Settings

Model CIMR-Po

4A0031

4A0038

4A0044

4A0058

o2-04

Drive Model Selection

Hex.

9C

9D

9E

9F

E2-11

Motor Rated Power

kW (HP)

15

(20)

18.5

(25)

22

(30)

30

(40)

b3-04

V/f Gain during Speed Search

%

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

b3-26

Start Speed Search Select

b8-03

Energy Saving Control Filter Time Constant

s

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

126.26

115.74

103.58

92.54

C5-17

Motor Inertia

kgm

2

0.076

0.138

0.165

0.220

C6-02

Carrier Frequency Selection

7

7

7

7

E2-01

Motor Rated Current

A

26.5

32.9

38.6

52.3

E2-02

Motor Rated Slip

Hz

1.6

1.67

1.7

1.8

E2-03

Motor No-Load Current

A

7.6

7.8

9.2

10.9

E2-05

Motor Line-to-Line Resistance

Ω

0.55

0.403

0.316

0.269

E2-06

Motor Leakage Inductance

%

17.2

20.1

23.5

20.7

E2-10

Motor Iron Loss for Torque Compensation

W

440

508

586

750

L2-02

Momentary Power Loss Ride-Thru Time

s

2

2

2

2

L2-03

Momentary Power Loss Minimum Baseblock Time

s

1

1

1

1.1

L2-04

Momentary Power Loss Voltage Recovery Time

s

0.6

0.6

0.6

0.6

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.244

0.317

0.355

0.323

L8-02

Overheat Alarm Level

°C

120

120

115

120

L8-35

Installation Method Selection

2

2

2

0

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

B.15 Defaults by Drive Model

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

473

B

Parameter List

This manual is related to the following products: