B.7 H Parameters: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.

u

H1: Multi-Function Digital Inputs

No.

(Addr.

Hex)

Name

Description

Values

Page

H1-01

(438)

Multi-Function Digital Input

Terminal S1 Function

Selection

Assigns a function to the multi-function digital inputs.

Refer to pages

433

to

435

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 40 (F)

<1>

Min.: 1

Max.: 9F

204

H1-02

(439)

Multi-Function Digital Input

Terminal S2 Function

Selection

Assigns a function to the multi-function digital inputs.

Refer to pages

433

to

435

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 41 (F)

<1>

Min.: 1

Max.: 9F

204

H1-03

(400)

Multi-Function Digital Input

Terminal S3 Function

Selection

Assigns a function to the multi-function digital inputs.

Refer to pages

433

to

435

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 24

Min.: 0

Max.: 9F

204

H1-04

(401)

Multi-Function Digital Input

Terminal S4 Function

Selection

Assigns a function to the multi-function digital inputs.

Refer to pages

433

to

435

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 14

Min.: 0

Max.: 9F

204

H1-05

(402)

Multi-Function Digital Input

Terminal S5 Function

Selection

Assigns a function to the multi-function digital inputs.

Refer to pages

433

to

435

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 3 (0)

<1>

Min.: 0

Max.: 9F

204

H1-06

(403)

Multi-Function Digital Input

Terminal S6 Function

Selection

Assigns a function to the multi-function digital inputs.

Refer to pages

433

to

435

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 4 (3)

<1>

Min.: 0

Max.: 9F

204

H1-07

(404)

Multi-Function Digital Input

Terminal S7 Function

Selection

Assigns a function to the multi-function digital inputs.

Refer to pages

433

to

435

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 6 (4)

<1>

Min.: 0

Max.: 9F

204

H1-08

(405)

Multi-Function Digital Input

Terminal S8 Function

Selection

Assigns a function to the multi-function digital inputs.

Refer to pages

433

to

435

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 8 (6)

<1>

Min.: 0

Max.: 9F

204

<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).

H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

Description

Page

0

3-Wire sequence

Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)

Terminals S1 and S2 are automatically set up for the Run command and Stop command.

205

1

LOCAL/REMOTE selection

Open: REMOTE (parameter settings determine the source of the frequency Reference 1 or 2

(b1-01, b1-02 or b1-15, b1-16)

Closed: LOCAL, Frequency reference and Run command are input from the digital operator.

205

2

External reference 1/2 selection

Open: Run command and frequency reference source 1 (determined by b1-01 and b1-02)

Closed: Run command and frequency reference source 2 (determined by b1-15 and b1-16)

206

3

Multi-Step Speed Reference 1

When input terminals are set to Multi-Step Speed References 1 through 3, switching

combinations of those terminals will create a multi-step speed sequence using the frequency

references set in d1-01 through d1-08.

206

4

Multi-Step Speed Reference 2

When input terminals are set to Multi-Step Speed References 1 through 3, switching

combinations of those terminals will create a multi-step speed sequence using the frequency

references set in d1-01 through d1-08.

206

5

Multi-Step Speed Reference 3

When input terminals are set to Multi-Step Speed References 1 through 3, switching

combinations of those terminals will create a multi-step speed sequence using the frequency

references set in d1-01 through d1-08.

206

6

Jog reference selection

Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference

sources.

206

7

Accel/decel time selection 1

Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel time 2 (set

in C1-03, C1-04).

206

8

Baseblock command (N.O.)

Closed: No drive output

206

B.7 H Parameters: Multi-Function Terminals

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

433

B

Parameter List