Temperature derating – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 411

Three-Phase 600 V Class
Drive Model
Rated Current [A]
Normal Duty Rating (ND)
2 kHz
5 kHz
8 kHz
10 kHz
5A0062
62.0
61.3
49.7
41.9
5A0077
77.0
76.2
61.7
52.0
5A0099
99.0
80.0
55.1
–
Three-Phase 600 V Class
Drive Model
Rated Current [A]
Normal Duty Rating (ND)
2 kHz
3 kHz
5A0125
125.0
93.0
5A0145
145.0
108.0
5A0192
192.0
148.0
5A0242
242.0
187.0
u
Temperature Derating
To ensure the maximum performance life, the drive output current must be derated as shown in
installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. In order to ensure reliable
drive overload protection, set parameters L8-12 and L8-35 according to the installation conditions.
n
Parameter Settings
No.
Name
Description
Range
Def.
L8-12
Ambient
Temperature Setting
Adjust the drive overload (oL2) protection level when the drive is installed
in an environment that exceeds its ambient temperature rating.
-10 to +50
+40 °C
L8-35
Installation Method
Selection
0: IP00/Open-Chassis Enclosure
1: Side-by-Side Mounting
2: IP20/NEMA Type 1 Enclosure
3: Finless Drive or External Heatsink Installation
0 to 3
<1>
<1> Default setting is determined by drive model.
Setting 0: (Models 2A0250 to 2A0415 and 4A0208 to 4A0675)
Setting 2: (Models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242).
Setting 0: IP00/Open-Chassis Enclosure
Drive operation between -10 °C and +50 °C allows 100% continuous current without derating.
Setting 1: Side-by-Side Mounting
Drive operation between -10 °C and +30 °C allows 100% continuous current without derating. Operation between +30 °C and
+50 °C requires output current derating.
Setting 2: IP20/NEMA Type 1 Enclosure
Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and
+50 °C requires output current derating.
Setting 3: External Heatsink Installation, Finless Drive
Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and
+50 °C requires output current derating.
A.4 Drive Derating Data
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
411
A
Specifications