Setting 0: Standard
Setting 1: EZ Sleep/Wake-up

n

b5-90: EZ Sleep Unit

Sets the unit, range, and resolution of parameters b5-91 and b5-92.

No.

Name

Setting Range

Default

b5-90

EZ Sleep Unit

0, 1

<1>

0

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

Setting 0: Hz
Setting 1: RPM (number of motor poles must be entered)

n

b5-91: EZ Minimum Speed

Sets the PID minimum speed and integral lower limit.
The lower limit of the internal value is the higher of b5-34 and d2-02.

No.

Name

Setting Range

Default

b5-91

EZ Minimum Speed

0.0 to 400.0 Hz

<1>

or 0 to 24000 RPM

0.0

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

n

b5-92: EZ Sleep Level

When the drive output frequency (or speed) is at or below this level for the time set in b5-93, the drive will go to sleep.
The internal lower limit of this parameter is b5-91 (EZ Min Speed) + 1 Hz.

No.

Name

Setting Range

Default

b5-92

EZ Sleep Level

0.0 to 400.0 Hz

<1>

or 0 to 24000 RPM

0.0

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

n

b5-93: EZ Sleep Time

The drive will go to sleep when the drive output frequency is at or below the level set to b5-92 for the time set in this parameter.

No.

Name

Setting Range

Default

b5-93

EZ Sleep Tim

0.0 to 10000.0

<1>

5.0 s

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

n

b5-94: EZ Wake-up Level

If b5-95 is set to 0 (Absolute), the drive wakes-up when the PID Feedback (H3-oo = 20) drops below this level for the time

set in b5-96. For reverse-acting, the PID Feedback has to be above this level for the time set in b5-96.
If b5-95 is set to 1 (Setpoint Delta), the drive wakes-up when the PID Feedback (H3-oo = 20) drops below the PID Setpoint

minus this level (for normal acting PID) for the time set in b5-96. For reverse-acting, Wake-up level is PID Setpoint plus this

level. The PID Feedback has to be above the wake-up level for the time set in b5-96.

No.

Name

Setting Range

Default

b5-94

EZ Wake-up Level

0.00 to 600.00%

<1>

0.00

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

n

b5-95: EZ Wake-up Mode

Sets how the wake-up level is determined.

5.2 b: Application

170

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual