C6-03, C6-04, C6-05: Carrier Frequency Upper Limit, Lower Limit, Proportional Gain

These parameters set a user-defined or a variable carrier frequency. Set C6-02 to F to set the upper and lower limits and the

carrier frequency proportional gain.

No.

Parameter Name

Setting Range

Default

C6-03

Carrier Frequency Upper Limit

1.0 to 15.0 kHz

Determined by

C6-02

C6-04

Carrier Frequency Lower Limit

1.0 to 15.0 kHz

C6-05

Carrier Frequency Proportional Gain

0 to 99

Setting a Fixed User Defined Carrier Frequency

A carrier frequency between the fixed selectable values can be entered in parameter C6-03 when C6-02 is set to F.

In V/f Control, adjust parameter C6-04 to the same value as C6-03.

Setting a Variable Carrier Frequency (V/f Control)

In V/f Control, the carrier frequency can be set up to change linearly with the output frequency by setting the upper and lower

limits for the carrier frequency and the carrier frequency proportional gain (C6-03, C6-04, C6-05) as shown in

Figure 5.25

.

C6-03

C6-04

E1-04

x C6-05

Output Frequency

Output

Frequency

Max Output Frequency

Carrier Frequency

Figure 5.25 Carrier Frequency Changes Relative to Output Frequency

Note:

When C6-05 is set lower than 7, C6-04 is disabled and the carrier frequency will be fixed to the value set in C6-03.