Table 5.10 PID Feedback Sources
PID Feedback Source
Settings
Analog Input A1
Set H3-02 = B
Analog Input A2
Set H3-10 = B
Analog Input A3
Set H3-06 = B
Pulse Input RP
Set H6-01 = 1
Note:
A duplicate allocation of the PID feedback input will cause an oPE alarm.
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed in
feedback function is automatically enabled when a differential feedback input is assigned.
Table 5.11 PID Differential Feedback Sources
PID Differential Feedback Source
Settings
Analog Input A1
Set H3-02 = 16
Analog Input A2
Set H3-10 = 16
Analog Input A3
Set H3-06 = 16
Note:
A duplicate allocation of the PID differential feedback input will cause an oPE alarm.