b4: Timer Function

No.

(Addr.

Hex)

Name

Description

Values

Page

b4-01

(1A3)

Timer Function On-Delay

Time

Sets the on-delay and off-delay times for a digital timer output

(H2-oo=12).

The output is triggered by a digital input programmed to

H1-oo=18).

Default: 0.0 s

Min.: 0.0

Max.: 3000.0

159

b4-02

(1A4)

Timer Function Off-Delay

Time

Default: 0.0 s

Min.: 0.0

Max.: 3000.0

159

u

b5: PID Control

No.

(Addr.

Hex)

Name

Description

Values

Page

b5-01

(1A5)

PID Function Setting

0: Disabled

1: Enabled (PID output becomes output frequency reference, deviation D

controlled)

Default: 0

Range: 0, 1

163

b5-02

(1A6)

Proportional Gain Setting

(P)

Sets the proportional gain of the PID controller.

Default: 1.00

Min.: 0.00

Max.: 25.00

163

b5-03

(1A7)

Integral Time Setting (I)

Sets the integral time for the PID controller.

Default: 1.0 s

Min.: 0.0

Max.: 360.0

163

b5-04

(1A8)

Integral Limit Setting

Sets the maximum output possible from the integrator as a percentage of the

maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

163

b5-05

(1A9)

Derivative Time (D)

Sets D control derivative time.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

163

b5-06

(1AA)

PID Output Limit

Sets the maximum output possible from the entire PID controller as a

percentage of the maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

163

b5-07

(1AB)

PID Offset Adjustment

Applies an offset to the PID controller output. Set as a percentage of the

maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

163

b5-08

(1AC)

PID Primary Delay Time

Constant

Sets a low pass filter time constant on the output of the PID controller.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

163

b5-09

(1AD)

PID Output Level Selection 0: Normal output (direct acting)

1: Reverse output (reverse acting)

Default: 0

Range: 0, 1

164

b5-10

(1AE)

PID Output Gain Setting

Sets the gain applied to the PID output.

Default: 1.00

Min.: 0.00

Max.: 25.00

164

b5-11

(1AF)

PID Output Reverse

Selection

0: Negative PID output triggers zero limit.

1: Rotation direction reverses with negative PID output.

Note:

When using setting 1, make sure reverse operation is permitted

by b1-04.

Default: 0

Range: 0, 1

164

b5-12

(1B0)

PID Feedback Loss

Detection Selection

0: No fault. Digital output only.

1: Fault detection. Alarm output, drive continues operation.

2: Fault detection. Fault output, drive output is shut off.

3: No fault. Digital output only. No fault detection when PID control is

disabled.

4: Fault detection. Alarm is triggered and drive continues to run. Fault

detection even when PID is disabled.

5: Fault detection. Drive output shuts off. No fault detection when PID control

is disabled.

Default: 0

Range: 0 to 5

165

b5-13

(1B1)

PID Feedback Loss

Detection Level

Sets the PID feedback loss detection level as a percentage of the maximum

output frequency.

Default: 0%

Min.: 0

Max.: 100

165

B.3 b: Application

418

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual