D2: frequency upper/lower limits, Figure 5.27, Illustrates the multi-step speed selection – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 183: D2-01: frequency reference upper limit, D2-02: frequency reference lower limit, 4 d: reference settings

background image

d1-04

d1-05

d1-06

d1-07

d1-17

d1-12

d1-13

d1-14

d1-15

d1-16

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

FWD (REV) Run/Stop

Multi-step Speed Ref. 2

Multi-step Speed Ref. 3

Jog Reference

Time

Multi-step Speed Ref. 1

Multi-step Speed Ref. 4

Frequency

reference

d1-01

(A1)

d1-02

(A2)

d1-03

(A3)

Figure 5.27 Preset Reference Timing Diagram

u

d2: Frequency Upper/Lower Limits

Upper and lower frequency limits prevent motor speed from going above or below levels that may cause resonance or

equipment damage.

n

d2-01: Frequency Reference Upper Limit

Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency

references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.

No.

Parameter Name

Setting Range

Default

d2-01

Frequency Reference Upper Limit

0.0 to 110.0%

100.0%

n

d2-02: Frequency Reference Lower Limit

Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency

references.
If a lower reference than this value is entered, the drive will run at the limit set to d2-02. If the drive is started with a lower

reference than d2-02, it will accelerate up to d2-02.

No.

Parameter Name

Setting Range

Default

d2-02

Frequency Reference Lower Limit

0.0 to 110.0%

0.0%

5.4 d: Reference Settings

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

183

5

Parameter Details