O2: digital operator keypad functions, O3: copy function, O4: maintenance monitor settings – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 450

background image

No.

(Addr.

Hex)

Name

Description

Values

Page

o1-15

(3107)

Frequency Reference and

Frequency Related Monitor

Custom Units 3

Sets the third character of the customer-specified unit display when o1-03 is

set to 3 and o1-09 is set to 24.

Default: 41

Range: 30 to 7A

268

<1> Default setting is dependent on parameter o1-03, Digital Operator Display Selection.

u

o2: Digital Operator Keypad Functions

No.

(Addr.

Hex)

Name

Description

Values

Page

o2-01

(505)

LO/RE Key Function

Selection

0: Disabled

1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.

Default: 1

Range: 0, 1

268

o2-02

(506)

STOP Key Function

Selection

0: Disabled. STOP key is disabled in REMOTE operation.

1: Enabled. STOP key is always enabled.

Default: 1

Range: 0, 1

269

o2-03

(507)

User Parameter Default

Value

0: No change.

1: Set defaults. Saves parameter settings as default values for a User

Initialization.

2: Clear all. Clears the default settings that have been saved for a User

Initialization.

Default: 0

Range: 0 to 2

269

o2-04

(508)

Drive Model Selection

Enter the drive model. Setting required only if installing a new control board. Default:

Determined by

drive capacity

269

o2-05

(509)

Frequency Reference

Setting Method Selection

0: ENTER key must be pressed to enter a frequency reference.

1: ENTER key is not required. The frequency reference can be adjusted using

the up and down arrow keys only.

Default: 0

Range: 0, 1

269

o2-06

(50A)

Operation Selection when

Digital Operator is

Disconnected

0: The drive continues operating if the digital operator is disconnected.

1: An oPr fault is triggered and the motor coasts to stop.

Default: 1

Range: 0, 1

270

o2-07

(527)

Motor Direction at Power

Up when Using Operator

This parameter requires assigning drive operation to the digital operator.

0: Forward

1: Reverse

Default: 0

Range: 0, 1

270

o2-20

(81E)

Operator RUN Save at

Power Loss

When running during a power loss, the Run command is issued via the digital

operator and the Run state is saved to the EEPROM.

When power is restored, the Run command is automatically applied if the

LOCAL/REMOTE or FREF conditions have not changed in the drive.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

270

u

o3: Copy Function

No.

(Addr.

Hex)

Name

Description

Values

Page

o3-01

(515)

Copy Function Selection

0: No action

1: Read parameters from the drive, saving them onto the digital operator.

2: Copy parameters from the digital operator, writing them to the drive.

3: Verify parameter settings on the drive to check if they match the data saved

on the operator.

Default: 0

Range: 0 to 3

271

o3-02

(516)

Copy Allowed Selection

0: Read operation prohibited

1: Read operation allowed

Default: 0

Range: 0, 1

271

u

o4: Maintenance Monitor Settings

No.

(Addr.

Hex)

Name

Description

Values

Page

o4-01

(50B)

Cumulative Operation Time

Setting

Sets the value for the cumulative operation time of the drive in units of 10 h. Default: 0

Min.: 0

Max.: 9999

271

o4-02

(50C)

Cumulative Operation Time

Selection

0: Logs power-on time

1: Logs operation time when the drive output is active (output operation time).

Default: 0

Range: 0, 1

271

B.10 o: Operator-Related Settings

450

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual