Three-Phase 200 V Class Drive Models 2A0040 to 2A0211
Table A.2 Power Ratings Continued (Three-Phase 200 V Class)
Item
Specification
Drive Model
2A0040 2A0056 2A0069 2A0081 2A0110 2A0138 2A0169 2A0211
Maximum Applicable
Motor Capacity (HP)
<1>
ND Rating
15
20
25
30
40
50
60
75
Input
Input Current (A)
<2>
ND Rating
52
68
80
96
111
136
164
200
Rated Voltage
Rated Frequency
Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc
<3>
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
ND Rating
27
36
44
52
51
62
75
91
Output
Rated Output Capacity
(kVA)
<4>
ND Rating
<5>
15.2
21
26
31
42
53
64
80
Rated Output Current (A)
ND Rating
<5>
40
56
69
81
110
138
169
211
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable between 1 and 15 kHz
<5>
User-adjustable
between 1 and
10 kHz
<5>
Maximum Output Voltage (V)
Three-phase 200 to 240 V (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings
raise the carrier frequency and require current derating.
A.1 Power Ratings