B.15 defaults by drive model – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 469

background image

No.

Name

Unit

Default Settings

Model CIMR-Po

2A0110

2A0138

2A0169

2A0211

o2-04

Drive Model Selection

Hex.

70

72

73

74

E2-11

Motor Rated Power

kW (HP)

30

(40)

37

(50)

45

(60)

55

(75)

b3-04

V/f Gain during Speed Search

%

80

80

80

80

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

b3-26

Start Speed Search Select

b8-03

Energy Saving Control Filter Time Constant

s

0.50

0.50

0.50

2.00

b8-04

Energy Saving Coefficient Value

46.27

38.16

35.78

31.35

C5-17

Motor Inertia

kgm

2

0.220

0.273

0.333

0.490

C6-02

Carrier Frequency Selection

7

7

7

7

E2-01

Motor Rated Current

A

105

131

160

190

E2-02

Motor Rated Slip

Hz

1.8

1.33

1.6

1.43

E2-03

Motor No-Load Current

A

21.9

38.2

44

45.6

E2-05

Motor Line-to-Line Resistance

Ω

0.064

0.039

0.03

0.022

E2-06

Motor Leakage Inductance

%

20.8

18.8

20.2

20.5

E2-10

Motor Iron Loss for Torque Compensation

W

699

823

852

960

L2-02

Momentary Power Loss Ride-Thru Time

s

2

2

2

2

L2-03

Momentary Power Loss Minimum Baseblock Time

s

1.1

1.1

1.2

1.3

L2-04

Momentary Power Loss Voltage Recovery Ramp Time

s

0.6

0.6

1

1

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.323

0.32

0.387

0.317

L8-02

Overheat Alarm Level

°C

130

130

130

125

L8-35

Installation Method Selection

0

0

0

0

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

B.15 Defaults by Drive Model

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

469

B

Parameter List