5 e: motor parameters – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 191

background image

Table 5.16 Predefined V/f Patterns

Setting

Specification

Characteristic

Application

0

50 Hz

Constant torque

For general purpose applications. Torque remains constant

regardless of changes to speed.

1

60 Hz

2

60 Hz (with 50 Hz base)

3

72 Hz (with 60 Hz base)

4

50 Hz, Variable torque 1

Variable torque

For fans, pumps, and other applications where the required

torque changes as a function of the speed.

5

50 Hz, Variable torque 2

6

60 Hz, Variable torque 1

7

60 Hz, Variable torque 2

8

50 Hz, mid starting torque

High starting torque

Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.

9

50 Hz, high starting torque

A

60 Hz, mid starting torque

B

60 Hz, high starting torque

C

90 Hz (with 60 Hz base)

Constant output

Output voltage is constant when operating at greater than

60 Hz.

D

120 Hz (with 60 Hz base)

E

180 Hz (with 60 Hz base)

F

<1>

60 Hz

Constant torque

For general purpose applications. Torque remains constant

regardless of changes to speed.

<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04

to E1-13 are the same as those of setting 1.

The following tables show details on predefined V/f patterns.

Predefined V/f Patterns for Models 2A0004 to 2A0021, 4A0002 to 4A0011, and 5A0003 to 5A0009

The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the

values by 2.875 for 600 V drives.

Table 5.17 Constant Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

9

200

1.3 2.5

50

15

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

60

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 5.18 Derated Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

8

200

1.3

25

50

35

V

oltage (V)

Frequency (Hz)

0

9

200

1.3

25

50

50

V

oltage (V)

Frequency (Hz)

0

8

200

1.5

30

60

35

V

oltage (V)

Frequency (Hz)

0

9

200

1.5

30

60

50

V

oltage (V)

Frequency (Hz)

Table 5.19 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

11

200

1.3 2.5

50

19

V

oltage (V)

Frequency (Hz)

0

13

200

1.3 2.5

50

24

V

oltage (V)

Frequency (Hz)

0

11

200

1.5 3

60

19

V

oltage (V)

Frequency (Hz)

0

15

200

1.5 3

60

24

V

oltage (V)

Frequency (Hz)

5.5 E: Motor Parameters

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

191

5

Parameter Details