Table 5.16 Predefined V/f Patterns
Setting
Specification
Characteristic
Application
0
50 Hz
Constant torque
For general purpose applications. Torque remains constant
regardless of changes to speed.
1
60 Hz
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Variable torque 1
Variable torque
For fans, pumps, and other applications where the required
torque changes as a function of the speed.
5
50 Hz, Variable torque 2
6
60 Hz, Variable torque 1
7
60 Hz, Variable torque 2
8
50 Hz, mid starting torque
High starting torque
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.
9
50 Hz, high starting torque
A
60 Hz, mid starting torque
B
60 Hz, high starting torque
C
90 Hz (with 60 Hz base)
Constant output
Output voltage is constant when operating at greater than
60 Hz.
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
F
<1>
60 Hz
Constant torque
For general purpose applications. Torque remains constant
regardless of changes to speed.
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are the same as those of setting 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models 2A0004 to 2A0021, 4A0002 to 4A0011, and 5A0003 to 5A0009
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V drives.
Table 5.17 Constant Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
9
200
1.3 2.5
50
15
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
60
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 5.18 Derated Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
8
200
1.3
25
50
35
V
oltage (V)
Frequency (Hz)
0
9
200
1.3
25
50
50
V
oltage (V)
Frequency (Hz)
0
8
200
1.5
30
60
35
V
oltage (V)
Frequency (Hz)
0
9
200
1.5
30
60
50
V
oltage (V)
Frequency (Hz)
Table 5.19 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
11
200
1.3 2.5
50
19
V
oltage (V)
Frequency (Hz)
0
13
200
1.3 2.5
50
24
V
oltage (V)
Frequency (Hz)
0
11
200
1.5 3
60
19
V
oltage (V)
Frequency (Hz)
0
15
200
1.5 3
60
24
V
oltage (V)
Frequency (Hz)
5.5 E: Motor Parameters
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
191
5