Digital Operator Display
Minor Fault Name
EF0
Option Card External Fault
An external fault condition is present.
Cause
Possible Solutions
An external fault was received from the
PLC with F6-03 set to 3, which allows the
drive to continue running after an external
fault occurs.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
There is a problem with the PLC program. Check the PLC program and correct problems.
Digital Operator Display
Minor Fault Name
EF1
External Fault (Input Terminal S1)
External fault at multi-function input terminal S1.
EF2
External fault (input terminal S2)
External fault at multi-function input terminal S2.
EF3
External fault (input terminal S3)
External fault at multi-function input terminal S3.
EF4
External fault (input terminal S4)
External fault at multi-function input terminal S4.
EF5
External fault (input terminal S5)
External fault at multi-function input terminal S5.
EF6
External fault (input terminal S6)
External fault at multi-function input terminal S6.
EF7
External fault (input terminal S7)
External fault at multi-function input terminal S7.
EF8
External fault (input terminal S8)
External fault at multi-function input terminal S8.
Cause
Possible Solutions
An external device has tripped an alarm
function.
Remove the cause of the external fault and reset the multi-function input value.
Wiring is incorrect.
• Ensure the signal lines have been connected properly to the terminals assigned for external fault detection
(H1-oo = 2C to 2F).
• Reconnect the signal line.
Multi-function contact inputs are set
incorrectly.
• Check if the unused terminals have been set for H1-oo = 2C to 2F (External Fault).
• Change the terminal settings.
Digital Operator Display
Minor Fault Name
EoF
EoF
Emergency Override Forward Run
Cause
Possible Solution
The multi-function digital input for
EmergOverrideFWD (H1-oo = AF) has
been closed.
Open H1-oo = AF if the emergency condition is no longer present
Digital Operator Display
Minor Fault Name
Eor
Eor
Emergency Override Reverse Run
Cause
Possible Solution
The multi-function digital input for
EmergOverrideREV (H1-oo = B0) has
been closed.
Open H1-oo = B0 if the emergency condition is no longer present
Digital Operator Display
Minor Fault Name
FbH
Excessive PID Feedback
The PID feedback input is higher than the level set to b5-36 for longer than the time set to b5-37, and b5-12
is set to 1 or 4.
Cause
Possible Solutions
Parameter settings for b5-36 and b5-37 are
incorrect.
Check parameters b5-36 and b5-37.
6.5 Alarm Detection
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
313
6
Troubleshooting