European standards, Ce low voltage directive compliance, D.2 european standards – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 520: Area of use, Factory recommended branch circuit protection
D.2 European Standards
Figure D.1 CE Mark
The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in business
and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics
manufacturers, and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
• Low Voltage Directive: 2006/95/EC
• EMC Guidelines: 2004/108/EC
Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying
the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE
standards. After setting up the device, verify that conditions meet European standards.
Note:
600 V class drives (models 5oooooo) are not compliant with European Standards.
u
CE Low Voltage Directive Compliance
This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage
Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other
devices:
n
Area of Use
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN 664.
n
Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
.
NOTICE:
If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices
to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Table D.1 Factory Recommended Drive Branch Circuit Protection
Drive Model
Fuse Type
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
Three-Phase 200 V Class
2A0004
FWH-70B
70
2A0006
FWH-70B
70
2A0008
FWH-70B
70
2A0010
FWH-70B
70
2A0012
FWH-70B
70
2A0018
FWH-90B
90
2A0021
FWH-90B
90
2A0030
FWH-100B
100
2A0040
FWH-200B
200
2A0056
FWH-200B
200
2A0069
FWH-200B
200
2A0081
FWH-300A
300
2A0110
FWH-300A
300
D.2 European Standards
520