For Reverse Acting PID, the PID Feedback must rise above the b5-94 level for the time set in b5-96 in order for the drive to

wake-up.
Wake-up using Setpoint Delta Level (b5-95 = 1)
For Normal Acting PID, the wake-up level is determined by the PID Setpoint minus the b5-94 level. The PID Feedback must

drop below the wake-up level for the time set in b5-96 in order for the drive to wake-up
For Reverse Acting PID, the wake-up level is determined by the PID Setpoint plus the b5-94 level. The PID Feedback must

rise above the wake-up level for the time set in b5-96 in order for the drive to wake-up.
Refer to

Figure 5.19

and

Figure 5.20

for detailed diagrams of EZ Sleep/Wake-up functions.

PID Set-point

Run Command

Output Frequency

Wake-up Level <1>

b5 -96

Minimum Speed

(b5-91) <2>

b5 -93

b5 -93

Wake-up

Level

reached

Wake-up

Timer

expired

Sleep

Level

reached

Sleep

Level

reached

Sleep
Timer

expired

Above

Sleep

Level

b5-9 6

b5-9 6

b5-96

Wake-up

Level

reached

Wake-up

Timer

expired

Wake-up

Level

reached

Wake-up

Level

reached

Above

Wake-up

Level

Above

Wake-up

Level

<1> Determined by EZ Wake-up Level (b5-94) and EZ Wake-up Mode (b5-95)

<2> EZ Sleep Level (b 5-92) is left at default (0.0 Hz), thus effectively making b 5-91 the Sleep Level

PID Feedback

Sleeping

Sleeping

Figure 5.19 EZ Sleep/Wake-up with Normal Acting PID and b5-92 = 0.0 Hz

Wake-up

Level

reached

Wake-up

Timer

expired

Sleep

Level

reached

Sleep
Timer

expired

Wake-up

Level

reached

Wake-up

Timer

expired

Wake-up

Level

reached

Wake-up

Level

reached

Above

Wake-up

Level

Above

Wake-up

Level

PID Set-point

Run Command

Output Frequency

Wake-up Level <1>

Minimum Speed

(B5-91)

PID Feedback

EZ Sleep Level

(B5-92)

<1> Determined by EZ Wake-up Level (B5-94) and EZ Wake-up Mode (B5-95)

b5-96

b5-93

b5-96

b5-96

b5-96

Sleeping

Figure 5.20 EZ Sleep/Wake-up with Reverse Acting PID and b5-92 > b5-91

n

b5-20: PID Setpoint Scaling

Determines the units for the PID Setpoint Value (b5-19) and monitors U5-01 and U5-04.

No.

Parameter Name

Setting Range

Default

b5-20

PID Setpoint Scaling

0 to 3

1

Setting 0: 0.01 Hz

The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.