H2-01, H2-02, H2-03

Setting

Description

B

Torque detection 1, N.O. (output closes when overload or underload is detected)

17

Torque detection 1, N.C. (output opens when overload or underload is detected)

18

Torque detection 2, N.O. (output closes when overload or underload is detected)

19

Torque detection 2, N.C. (output opens when overload or underload is detected)

Figure 5.82

and

Figure 5.83

illustrate the functions of overtorque and undertorque detection.

Motor current / torque

L6-02/05

10 % hysteresis

Torque detection 1 (NO)

or

Torque detection 2 (NO)

L6-03/06

ON

L6-03/06

10 % hysteresis

ON

Figure 5.82 Overtorque Detection Operation

Motor current / torque

L6-02/05

10 % hysteresis

Torque detection 1 (NO)

or

Torque detection 2 (NO)

L6-03/06

ON

L6-03/06

ON

Figure 5.83 Undertorque Detection Operation

Note:

1. The torque detection function uses a hysteresis of 10% of the drive rated output current and motor rated torque.
2. The level is set as a percentage of the drive rated output current. .

n

L6-01, L6-04: Torque Detection Selection 1, 2

The torque detection function is triggered when the current or torque exceed the levels set to L6-02 and L6-05 for longer than

the times set to L6-03 and L6-06. L6-01 and L6-04 select the conditions for detection and the operation that follows.

No.

Name

Setting Range

Default

L6-01

Torque Detection Selection 1

0 to 12

0

L6-04

Torque Detection Selection 2

0 to 8

0

Setting 0: Disabled

Setting 1: oL3, oL4 at speed agree (Alarm)

Overtorque detection is active only when the output speed is equal to the frequency reference (i.e., no detection during

acceleration and deceleration). The operation continues after detecting overtorque and triggering an oL3/oL4 alarm.

Setting 2: oL3, oL4 at run (Alarm)

Overtorque detection works as long as the Run command is active. The operation continues after detecting overtorque and

triggering an oL3/oL4 alarm.

Setting 3: oL3, oL4 at speed agree (Fault)

Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during

acceleration and deceleration. The operation stops and triggers an oL3/oL4 fault.

Setting 4: oL3, oL4 at run (Fault)

Overtorque detection works as long as a Run command is active. The operation stops and triggers an oL3/oL4 fault.