Name

(Parameter No.)

Application

Stall Prevention

(L3-01 through L3-06, L3-11)

• Prevents motor speed loss and overvoltage when the load is too heavy or during sudden acceleration/

deceleration.

• Adjustment is not normally necessary because Stall Prevention is enabled as a default. Set L3-04 to 0 to

disable Stall Prevention during deceleration when using a braking resistor.

6.2 Motor Performance Fine-Tuning