Drive Model
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
2A0021
R/L1, S/L2, T/L3
10
12 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
10
12 to 10
⊖, ⊕1, ⊕2
–
12 to 10
B1, B2
–
14 to 10
10
<1>
12 to 10
2A0030
R/L1, S/L2, T/L3
8
10 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
8
10 to 6
⊖, ⊕1, ⊕2
–
10 to 6
B1, B2
–
14 to 10
8
<2>
10 to 8
M5
2.0 to 2.5
(17.7 to 22.1)
2A0040
R/L1, S/L2, T/L3
6
8 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
8
8 to 6
⊖, ⊕1, ⊕2
–
6
B1, B2
–
12 to 10
8
<2>
10 to 8
M5
2.0 to 2.5
(17.7 to 22.1)
2A0056
R/L1, S/L2, T/L3
4
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3
4
6 to 4
⊖, ⊕1, ⊕2
–
6 to 4
B1, B2
–
10 to 6
M5
2.7 to 3.0
(23.9 to 26.6)
6
8 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
2A0069
R/L1, S/L2, T/L3
3
4 to 3
M8
9.9 to 11.0
(87.6 to 97.4)
U/T1, V/T2, W/T3
3
4 to 3
⊖, ⊕1, ⊕2
–
4 to 3
B1, B2
–
8 to 6
M5
2.7 to 3.0
(23.9 to 26.6)
6
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
2A0081
R/L1, S/L2, T/L3
2
3 to 2
M8
9.9 to 11.0
(87.6 to 97.4)
U/T1, V/T2, W/T3
2
3 to 2
⊖, ⊕1, ⊕2
–
3 to 2
B1, B2
–
6
M5
2.7 to 3.0
(23.9 to 26.6)
6
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
2A0110
R/L1, S/L2, T/L3
1/0
3 to 1/0
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
1/0
3 to 1/0
⊖, ⊕1
–
2 to 1/0
B1, B2
–
6 to 1/0
6
6 to 4
2A0138
R/L1, S/L2, T/L3
2/0
1 to 2/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
2/0
1 to 2/0
⊖, ⊕1
–
1/0 to 3/0
B1, B2
–
4 to 2/0
4
4
M8
9 to 11
(79.7 to 97.4)
2A0169
R/L1, S/L2, T/L3
4/0
2/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
4/0
3/0 to 4/0
⊖, ⊕1
–
1 to 4/0
⊕3
–
1/0 to 4/0
4
4 to 2
D.3 UL and CSA Standards
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
529
D
Standards Compliance