n

A1-06: Application Preset

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these

Application Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters

to values appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.

User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple

menus.

u

A2: User Parameters

n

A2-01 to A2-32: User Parameters 1 to 32

The user can select up to 32 parameters and assign them to parameters A2-01 through A2-32 to provide quicker access by

eliminating the need to scroll through multiple menus. The User Parameter list can also save the most recently edited

parameters.

No.

Parameter Name

Setting Range

Default

A2-01 to A2-32

User Parameters 1 to 32

b1-01 to s6–07

Determined by

A1-03

Saving User Parameters

To save specific parameters to A2-01 through A2-32, set parameter A1-01 to 2 to allow access to all parameters, then enter

the parameter number to one of the A2-oo parameters to assign it to the list of User Parameters. Finally, set A1-01 to 1 to

restrict access so users can only set and refer to the parameters saved as User Parameters.

n

A2-33: User Parameter Automatic Selection

Determines whether recently edited parameters are saved to the second half of the User Parameters (A2-17 to A2-32) for

quicker access.

No.

Parameter Name

Setting Range

Default

A2-33

User Parameter Automatic Selection

0, 1

0

Setting 0: Do not save list of recently edited parameters

Set A2-33 to 0 to manually select the parameters listed in the User Parameter group.

Setting 1: Save list of recently edited parameters

Set A2-33 to 1 to automatically save recently edited parameters to A2-17 through A2-32. A total of 16 parameters are saved

with the most recently edited parameter set to A2-17, the second most recently to A2-18, and so on. Access the User Parameters

using the Setup Mode of the digital operator.