o4-03: Cooling Fan Operation Time Setting

Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03

also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after

replacing the cooling fan.

Note:

1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. “300”

will be displayed in monitor U4-03.

2. The cooling fan may require maintenance at an earlier date in harsher environments.

No.

Name

Setting Range

Default

o4-03

Cooling Fan Operation Time Setting

0 to 9999

0

n

o4-05: Capacitor Maintenance Setting

Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected

performance life. Reset this value to 0 after replacing the DC bus capacitors.

Note:

The actual maintenance time will depend on the environment where the drive is used.

No.

Name

Setting Range

Default

o4-05

Capacitor Maintenance Setting

0 to 150%

0%

n

o4-07: DC Bus Pre-Charge Relay Maintenance Setting

Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected

performance life. Reset this value to 0 after replacing the bypass relay.

Note:

The actual maintenance time will depend on the environment where the drive is used.

No.

Name

Setting Range

Default

o4-07

DC Bus Pre-charge Relay Maintenance Setting

0 to 150%

0%

n

o4-09: IGBT Maintenance Setting

Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life. Reset

this value to 0 after replacing the IGBTs.

Note:

The actual maintenance time will depend on the environment where the drive is used.

No.

Name

Setting Range

Default

o4-09

IGBT Maintenance Setting

0 to 150%

0%

n

o4-11: U2, U3 Initialization

Resets the fault trace and fault history monitors (U2-oo and U3-oo). Initializing the drive using A1-03 does not reset these

monitors.

No.

Name

Setting Range

Default

o4-11

U2, U3 Initialization

0, 1

0

Setting 0: No Action

The drive keeps the previously saved record concerning fault trace and fault history.

Setting 1: Reset Fault Data

Resets the data for the U2-oo and U3-oo monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and

returns the display to 0.

n

o4-12: kWh Monitor Initialization

Manually resets kWh monitors U4-10 and U4-11. Initializing the drive or cycling the power will not reset these monitors.

No.

Name

Setting Range

Default

o4-12

kWh Monitor Initialization

0, 1

0

Setting 0: No Action

The kWh data are maintained.