Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 506

Register No.
Contents
00CBH
Alarm Contents 5
bit 0
SI-T3 Watchdog Error (E5)
bit 1
SI-T3 Station Address Setting Error (AEr)
bit 2
SI-T3 Comm. Cycle Setting Error (CyC)
bit 3
High Current Alarm (HCA)
bit 4
Cooling Fan Maintenance Time (LT-1)
bit 5
Soft Charge Bypass Relay Maintenance Time (LT-2)
bit 6
Reserved
bit 7
SI-S EEPROM Error (EEP)
bit 8
External Fault 1 (input terminal S1) (EF1)
bit 9
External Fault 2 (input terminal S2) (EF2)
bit A to F
Reserved
00CCH
Alarm Contents 6
bit 0
Output Voltage Detection Fault (VoF)
bit 1
IGBT Maintenance Time (90%) (TrPC)
bit 2
Capacitor Maintenance Time (LT-3)
bit 3
IGBT Maintenance Time (50%) (LT-4)
bit 4
Braking Transistor Overload Fault (boL)
bit 5 to 6
Reserved
bit 7
Motor Overheat (NTC Input) (oH5)
bit 8 to B
Reserved
bit C
Thermistor Disconnect (THo)
bit D
Underload Detection 6 (UL6)
bit E
Waiting for Run (wRUn)
bit F
Reserved
00CDH
Reserved
00CEH
bit 0, 1
Reserved
bit 2
Time Not Set (TIM)
bit 3
Battery Low (bAT)
bit 4
Time Deviation Error (TdE)
bit 5
Reserved
bit 6
Emergency Override FWD (EoF)
bit 7
Emergency Override REV (Eor)
00CFH
Reserved
00D0H
CPF Contents 1
bit 0, 1
Reserved
bit 2
A/D Conversion Error (CPF02)
bit 3
PWM Data Fault (CPF03)
bit 4, 5
Reserved
bit 6
EEPROM Memory Data Error (CPF06)
bit 7
Terminal Board Connection Error (CPF07)
bit 8
EEPROM Serial Communications Fault (CPF08)
bit 9, A
Reserved
bit B
RAM Fault (CPF11)
bit C
FLASH Memory Fault (CPF12)
bit D
Watchdog Circuit Exception (CPF13)
bit E
Control Circuit Fault (CPF14)
bit F
Reserved
C.9 MEMOBUS/Modbus Data Table
506