PID feedback wiring is faulty.

Correct the wiring.

Feedback sensor has malfunctioned.

Check the sensor and replace it if damaged.

Feedback input circuit is damaged.

Replace either the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or your nearest sales representative.

Digital Operator Display

Minor Fault Name

FbL

PID Feedback Loss
The PID feedback input is lower than the level set to b5-13 for longer than the time set to b5-14.

Cause

Possible Solutions

Parameter settings for b5-13 and b5-14 are

incorrect.

Check parameters b5-13 and b5-14.

PID feedback wiring is faulty.

Correct the wiring.

Feedback sensor has malfunctioned.

Check the sensor and replace it if damaged.

Feedback input circuit is damaged.

Replace either the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or your nearest sales representative.

Digital Operator Display

Minor Fault Name

HCA

Current Alarm
Drive current exceeded overcurrent warning level (150% of the rated current).

Cause

Possible Solutions

Load is too heavy.

Reduce the load for applications with repetitive operations (i.e., stops and starts), or replace the drive.

Acceleration and deceleration times are too

short.

• Calculate the torque required during acceleration and for the inertia moment.
• If the torque level is not right for the load, take the following steps:
• Increase the acceleration and deceleration times (C1-01 through C1-04).
• Increase the capacity of the drive.

A special-purpose motor is being used, or

the drive is attempting to run a motor

greater than the maximum allowable

capacity.

• Check the motor capacity.
• Use a motor appropriate for the drive. Ensure the motor is within the allowable capacity range.

The current level increased due to Speed

Search after a momentary power loss or

while attempting to perform a fault restart.

The alarm will only appear briefly. There is no need to take action to prevent the alarm from occurring in

such instances.

Digital Operator Display

Minor Fault Name

LT-1

Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.

Note:

An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F and

H2-oo = 10) are set.

Cause

Possible Solutions

The cooling fan has reached 90% of its

expected performance life.

Replace the cooling fan and set o4-03 to 0 to reset the Maintenance Monitor.

Digital Operator Display

Minor Fault Name

LT-2

Capacitor Maintenance Time

The main circuit and control circuit capacitors are nearing the end of their expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solutions

The main circuit and control circuit

capacitors have reached 90% of their

expected performance lives.

Replace either the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or your nearest sales representative.

Digital Operator Display

Minor Fault Name

LT-3

Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solutions

6.5 Alarm Detection

314

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual